IEC 60364-5-52 NEC 310.16 GB 16895 Voltage-drop check

Cable size calculator

Professional wire cross-section sizing by current or power — IEC, NEC (USA) and GB (China) standards, with voltage-drop check and ready-to-order cable options.

Parameters

IEC 60364-5-52 — cross-section in mm². Used across Europe and most of the world.
kW
V
°C
m
%
Recommended conductor
Enter a value to see the recommendation.
Installation method

Cable options

Nearest standard size that carries the load with your installation conditions and stays within the voltage-drop limit.

Size Ampacity V-drop Status

How the sizing works

1 · Load current

From power the current is Ib = P / (V · cos φ) for single-phase, or Ib = P / (√3 · V · cos φ) for three-phase. Enter current directly to skip this step.

2 · Correction factors

The table ampacity of every size is corrected for installation method, ambient temperature and grouping. A conductor is valid only when its corrected ampacity is at least the design current.

3 · Voltage drop

Drop is ΔU = k · I · L · ρ / S (k = 2 single-phase, √3 three-phase; ρ = 0.0175 Ω·mm²/m copper, 0.0282 aluminium). If a size exceeds your limit it is rejected even when its ampacity is enough.

4 · Recommendation

The smallest size passing both checks is recommended; nearby sizes are listed as alternatives, with the closest equivalent shown in the other standards.

Add this widget to your site

Free, ready-to-embed cable calculator — pick a style and your brand color, copy the snippet, done. It loads in an iframe, so it never clashes with your page styles.

Live preview
Important

This tool gives a fast engineering estimate for typical PVC/XLPE insulated cables. Correction factors are simplified. Final conductor and protective-device selection must follow the full local wiring code (IEC 60364, NEC/NFPA 70, GB 50054, etc.) and, where required, be approved by a qualified electrical engineer.